Arc Flash Hazard report indicates a trip device that is upstream to the trip device I expect will trip first

Check to see if the protective devices are well coordinated. You can plot the TCC for both devices. Any overlap indicates miscoordination, which is not uncommon.

EasyPower selects the fastest tripping device for series path. For parallel paths, the slowest tripping device is selected for conservative results.